ZhiJingLing VRV — Home Assistant Integration

Native Home Assistant control for ZhiJingLing (智精靈) VRV air-conditioning systems
Up to 64 indoor units over a single Modbus TCP gateway. Local-poll. No cloud. HACS-ready.

OverviewFeaturesArchitectureProtocolInstallationConfigurationVerified BehaviourTroubleshooting繁體中文

Home Assistant 2024.10+ Python 3.12+ pymodbus 3.11.2+ HACS Custom local_polling License MIT Verified on HAOS 2026.4.2


Overview

ZhiJingLing VRV is a first-party Home Assistant custom integration for the 智精靈 Modbus-TCP VRV gateway — the small industrial-grade converter that sits between a Daikin/Mitsubishi/Panasonic VRV bus and your LAN. It exposes every indoor unit (IDU) behind the gateway as a native climate.* entity, so the whole VRV system becomes controllable and automatable inside Home Assistant with no cloud, no vendor app, no polling scripts.

Under the hood: a single DataUpdateCoordinator performs batched FC03 reads across all 64 IDU slots every 10 seconds, translates the vendor register encoding into HA-native HVACMode / fan_mode / temperature, and dispatches new IDUs onto the platform as they come online. Writes go through FC16 (write-multiple-registers) so set_hvac_mode / set_temperature / set_fan_mode / turn_off all round-trip cleanly.

Why this integration?

Pain point without this integration What ZhiJingLing VRV gives you
Vendor app is Chinese-only, phone-only, cloud-only Native HA climate entities — voice, dashboards, automations, HomeKit / Google / Alexa via HA
Building has 64 IDUs and no per-room automation Every IDU = one entity, ready for schedules, presence, temperature sensors
Modbus TCP is raw registers, not HA-friendly Register semantics abstracted (mode, fan, setpoint, room temp, fault)
Gateway or LAN drops → HA gets stuck on stale values Coordinator flips entities to unavailable; auto-recovers on next successful poll
Adding an IDU later means reconfiguring HA Newly-online IDUs are added dynamically via dispatcher signal — no restart
Modbus setpoint range varies per install Reads gateway-programmed temp_min / temp_max at handshake, falls back to 16 – 30 °C
Vendor SDK is proprietary 100 % open, pymodbus>=3.11.2, TDD-covered, config-flow driven

Live evidence

Task 10 smoke test against a live 64-IDU gateway, 2026-07-29:

  • 64 climate entities (climate.nei_ji_1climate.nei_ji_64)
  • 2 diagnostic sensors (sensor.zhi_jing_ling_vrv_zha_dao_idu_total = 64, ..._idus_online = 64)
  • Write path: set_hvac_modeset_temperatureset_fan_modeturn_off all round-tripped
  • Kill-restore: blackhole-routed the gateway for 45 s → HA marked entities unavailable; on restoration entities came back with prior state preserved, no HA restart needed

Full log: docs/smoke-test-2026-07-29.md.


Features

Core capabilities

  • 64 IDUs on one gateway — one Modbus TCP link fans out into 64 native climate entities
  • Local polling — no cloud, no vendor account, 10 s scan interval, iot_class: local_polling
  • Config flow only — no YAML; add via Settings → Devices & Services → Add integration
  • Dynamic IDU discovery — new IDUs powered up post-setup appear automatically (dispatcher signal, no restart)
  • Automatic recovery — gateway drop → entities unavailable; gateway back → next poll reconciles state
  • TDD-covered — coordinator parsing and const tables ship with pytest suites (see tests/)

Per-IDU climate entity

Each climate.nei_ji_N exposes:

Attribute Values Notes
hvac_modes off / heat / cool / fan_only / dry mapped from vendor mode register
fan_modes auto / low / medium / high mapped from vendor fan_speed register
current_temperature int16 °C from IDU sensor signed — negative values pass through
target_temperature °C, step 1 bounded by gateway-reported temp_min/temp_max (fallback 16 – 30)
extra_state_attributes.fault_code 0 = healthy, non-zero = vendor fault code pass-through for automations
available false when IDU offline (room=0, on/off=0, fault=0 all zero) heuristic per §3 of protocol

Behavioural guards:

  • Cannot change setpoint in fan_only mode → raises ServiceValidationError
  • Cannot change fan speed in dry mode → raises ServiceValidationError
  • Writing to an offline IDU raises HomeAssistantError("IDU N offline; cannot write")

Diagnostic sensors

Entity Meaning
sensor.zhi_jing_ling_vrv_zha_dao_idu_total Gateway-reported total IDUs on the bus
sensor.zhi_jing_ling_vrv_zha_dao_idus_online Currently online IDUs (0 – 64) — dashboard-friendly liveness signal

Supported gateway inputs (config-flow)

Field Default Range
Host (required) any resolvable IP / hostname
Port 502 1 – 65535
Slave ID 1 1 – 247

Validation at handshake: gateway must reply to read_holding_registers(2000, 6) and report 1 ≤ idu_total ≤ 64, otherwise the config flow rejects with invalid_device.


Architecture

Component topology

flowchart TB
    subgraph HA["Home Assistant Core"]
        UI["Dashboards / Automations / Voice"]
        CE["climate.nei_ji_1 … climate.nei_ji_64"]
        SE["sensor.idu_total / sensor.idus_online"]
        CF["Config Flow — 智精靈閘道"]
    end

    subgraph INT["custom_components/zhijingling_vrv"]
        CFP["config_flow.py<br/>host / port / slave_id"]
        INIT["__init__.py<br/>AsyncModbusTcpClient + Coordinator"]
        COORD["coordinator.py<br/>DataUpdateCoordinator (10 s)"]
        CLIM["climate.py<br/>ZhijinglingClimate x N"]
        SENS["sensor.py<br/>diagnostic sensors"]
        CONST["const.py<br/>register map + encoding"]
    end

    subgraph NET["LAN"]
        GW["智精靈 VRV Gateway<br/>Modbus TCP :502  slave 1"]
        BUS["VRV Bus"]
        IDU["IDU 1 … IDU 64"]
    end

    UI --> CE
    UI --> SE
    CF --> CFP
    CFP -->|create_entry| INIT
    INIT -->|async_setup_entry| COORD
    COORD -->|async_add_entities| CLIM
    COORD -->|async_add_entities| SENS
    CE -.->|service calls| CLIM
    CLIM -->|async_write_idu| COORD
    COORD -->|FC03 / FC16| GW
    GW <--> BUS
    BUS <--> IDU

    classDef ha fill:#41BDF5,stroke:#00579C,color:#fff
    classDef int fill:#8BC34A,stroke:#33691E,color:#000
    classDef net fill:#FFB74D,stroke:#E65100,color:#000
    class UI,CE,SE,CF ha
    class CFP,INIT,COORD,CLIM,SENS,CONST int
    class GW,BUS,IDU net
Loading

Data flow (poll cycle)

sequenceDiagram
    autonumber
    participant HA as Home Assistant
    participant C as ZhijinglingCoordinator
    participant M as AsyncModbusTcpClient
    participant G as 智精靈 Gateway
    Note over C: SCAN_INTERVAL = 10 s
    HA->>C: _async_update_data()
    C->>M: read_holding_registers(2000, 6)
    M->>G: FC03 addr=2000 qty=6
    G-->>M: [brand, product_type, idu_total, temp_min, temp_max, _]
    M-->>C: registers
    C->>C: parse_gateway_meta()
    loop 5 batches × 15 IDUs (last batch 4)
        C->>M: read_holding_registers(base + n*6, 15*6)
        M->>G: FC03 addr qty=90
        G-->>M: 90 register values
        M-->>C: registers
        C->>C: parse_idu_batch()<br/>signed_int16 room_temp<br/>_is_online() heuristic
    end
    C->>C: diff new IDUs → SIGNAL_NEW_IDU
    C-->>HA: CoordinatorData{gateway, idus}
    HA->>HA: update all ClimateEntity + Sensor states
Loading

Write path

sequenceDiagram
    autonumber
    participant U as User / Automation
    participant HA as HA climate.set_temperature
    participant E as ZhijinglingClimate
    participant C as Coordinator
    participant G as Gateway
    U->>HA: temperature: 24
    HA->>E: async_set_temperature(24)
    E->>E: guard: not FAN_ONLY?
    E->>C: async_write_idu(idu_id=0, set_temp=24)
    C->>C: merge with cached IduState
    Note over C: payload = [on_off, mode, set_temp, fan]
    C->>G: FC16 write_registers(4000 + 0*4, [1,2,24,3])
    G-->>C: ACK
    C->>C: async_refresh() → immediate poll
    C-->>E: new state → entity updates in HA
Loading

Failure / recovery

stateDiagram-v2
    [*] --> Healthy
    Healthy --> Reading: every 10 s
    Reading --> Healthy: FC03 success
    Reading --> UpdateFailed: TCP timeout / Modbus error
    UpdateFailed --> Unavailable: coordinator marks entities unavailable
    Unavailable --> Reading: next 10 s tick
    Reading --> Healthy: FC03 success again
    Healthy --> WriteRequested: service call
    WriteRequested --> Healthy: FC16 success + refresh
    WriteRequested --> WriteError: IDU offline or Modbus error
    WriteError --> Healthy: raise ServiceValidationError / HomeAssistantError
Loading

Module dependency

flowchart LR
    manifest[manifest.json] --> pymodbus["pymodbus ≥ 3.11.2"]
    init["__init__.py"] --> coordinator["coordinator.py"]
    init --> config_flow["config_flow.py"]
    coordinator --> const["const.py"]
    climate["climate.py"] --> coordinator
    climate --> const
    sensor["sensor.py"] --> coordinator
    sensor --> const
    coordinator --> pymodbus
    init --> pymodbus
    config_flow --> pymodbus

    classDef core fill:#8BC34A,stroke:#33691E
    classDef dep fill:#FFB74D,stroke:#E65100
    class init,coordinator,climate,sensor,const,config_flow core
    class pymodbus,manifest dep
Loading

Modbus Protocol

Full reference: docs/protocol.md.

Gateway metadata — FC03 @ 2000 (length 6)

Offset Field Type Meaning
0 brand uint16 Vendor brand code
1 product_type uint16 VRV family code
2 idu_total uint16 Number of IDUs on bus (must be 1 – 64)
3 temp_min uint16 °C Installer-programmed minimum setpoint (0 = unset)
4 temp_max uint16 °C Installer-programmed maximum setpoint (0 = unset)
5 _reserved uint16 Reserved

Per-IDU read — FC03 @ 0 + 6·N (stride 6)

Offset Field Type Encoding
0 on_off uint16 0=off, 1=on
1 mode uint16 1=heat, 2=cool, 4=fan_only, 8=dry
2 set_temp uint16 °C Target temperature
3 fan_speed uint16 0=auto, 1=low, 2=medium, 3=high
4 room_temp int16 °C Signed — negative interpreted via two's complement
5 fault_code uint16 0 = healthy

Batched: 15 IDUs × 6 regs = 90 registers per FC03 — 64 IDUs are covered in 5 batches (0, 90, 180, 270, 360), keeping under the standard 125-register FC03 ceiling.

Per-IDU write — FC16 @ 4000 + 4·N (stride 4)

Offset Field
0 on_off
1 mode
2 set_temp
3 fan_speed

Writes are always the full 4-register payload. The coordinator reads the cached IduState, patches the changed field, and writes back all four. If no cache exists (never-seen IDU), it does a fallback FC03 first.

Online heuristic

def _is_online(on_off, room_temp, fault_code) -> bool:
    return room_temp != 0 or on_off != 0 or fault_code != 0

If all three are zero, the IDU slot is treated as not populated — filtered out of idus, no entity created, sensor.idus_online decremented.


Installation

Full step-by-step: docs/installation.md.

Option A — HACS (recommended)

  1. HACS → Integrations → ⋮ → Custom repositories
  2. Add https://github.com/WOOWTECH/Woow_ha_vrv_climate_component, category Integration
  3. Search ZhiJingLing VRVDownload
  4. Settings → System → Restart
  5. Settings → Devices & Services → Add integration → ZhiJingLing VRV

Option B — Manual

cd /config
git clone https://github.com/WOOWTECH/Woow_ha_vrv_climate_component /tmp/zjl
cp -r /tmp/zjl/custom_components/zhijingling_vrv custom_components/
# Restart Home Assistant

Or via the Samba / File-Editor add-on: copy the custom_components/zhijingling_vrv/ folder into /config/custom_components/, then restart HA.

Requirements

  • Home Assistant 2024.10.0 or newer
  • Python 3.12+ (matches HA Core runtime)
  • pymodbus>=3.11.2 — declared in manifest.json, installed automatically by HA on first setup
  • Network route from the HA host to the gateway on TCP 502

Configuration

Settings → Devices & Services → Add integration → ZhiJingLing VRV

Field Example Notes
Host 192.168.2.20 gateway LAN IP
Port 502 Modbus TCP default
Slave ID 1 1 – 247, per gateway rotary switch / firmware

At submit, the config flow calls read_holding_registers(2000, 6) against the gateway. Errors surface as:

  • cannot_connect — TCP connect failed (wrong IP, blocked port, gateway offline)
  • invalid_device — connect OK but the reply doesn't look like a ZhiJingLing gateway (bad idu_total)
  • unknown — unexpected exception; check home-assistant.log

Successful setup:

  • Entry title = 智精靈閘道 (<host>)
  • 64 IDU device entries appear under Devices, each with one climate entity
  • 2 diagnostic sensors attached to the gateway "hub" device

Gateway prep

The gateway's Modbus TCP mode must be enabled first via its built-in web UI:

菜单 → 网络 → 网络协议 → MODBUS-TCP — save, reboot the gateway.

Then confirm the slave-ID rotary matches 1 (default) and IDUs are addressed sequentially from IDU 1.


Verified Behaviour

Live smoke test against a real 64-IDU deployment. Full log: docs/smoke-test-2026-07-29.md.

Target: HAOS 2026.4.2 · Asia/Taipei · gateway 192.168.2.20:502 slave 1 · component 0.1.0

1. Config flow via REST

POST /api/config/config_entries/flow  {"handler":"zhijingling_vrv"}
→ flow_id 01KYQ4GCMFKD5DQK2D2KXQHSEX  step "user"

POST /api/config/config_entries/flow/01KYQ4GCMFKD5DQK2D2KXQHSEX
  {"host":"192.168.2.20","port":502,"slave_id":1}
→ type=create_entry  state=loaded
  title "智精靈閘道 (192.168.2.20)"

2. Entity discovery

  • 64 climate.nei_ji_1climate.nei_ji_64 (friendly names 內機 1 … 內機 64)
  • 2 sensors: sensor.zhi_jing_ling_vrv_zha_dao_idu_total = 64 · sensor.zhi_jing_ling_vrv_zha_dao_idus_online = 64
  • Initial states: IDU 1 = off; IDU 2 – 64 = cool

3. Write path — climate.nei_ji_1

Step Service call Post-write state
1 climate.set_hvac_mode hvac_mode: cool state=cool temperature=25.0 fan_mode=high
2 climate.set_temperature temperature: 24 state=cool temperature=24.0 fan_mode=high
3 climate.set_fan_mode fan_mode: auto state=cool temperature=24.0 fan_mode=auto
4 climate.turn_off state=off temperature=24.0 fan_mode=auto

All writes surfaced by the next coordinator refresh.

4. Kill-restore — blackhole route on the host, 45 s window

22:32:49  ip route add blackhole 192.168.2.20        # kill
22:33:15  coordinator: "Modbus Error: No response received after 3 retries"
22:33:32  probe:  climate.nei_ji_1 = unavailable
                  sensor idus_online = unavailable
22:33:34  ip route del blackhole 192.168.2.20        # restore
22:34:04  post:    climate.nei_ji_1 = off (setpoint 24, fan auto preserved)
                   sensor idus_online = 64
                   sensor idu_total   = 64

Recovery is fully automatic — no HA restart required.


Repository Layout

Woow_ha_vrv_climate_component/
├── custom_components/
│   └── zhijingling_vrv/
│       ├── __init__.py          # setup_entry, RuntimeData, pymodbus client
│       ├── config_flow.py       # host/port/slave_id + handshake validation
│       ├── const.py             # DOMAIN, register map, mode/fan tables
│       ├── coordinator.py       # DataUpdateCoordinator, batched FC03, FC16 write
│       ├── climate.py           # ZhijinglingClimate (one per IDU)
│       ├── sensor.py            # idu_total + idus_online diagnostic sensors
│       └── manifest.json        # HA integration manifest
├── tests/
│   ├── conftest.py              # opt-in asyncio.sleep patch
│   ├── test_const.py            # protocol constant regression
│   ├── test_coordinator_parse.py
│   └── test_coordinator_poll.py
├── docs/
│   ├── architecture.md          # deep dive: setup, coordinator, entities, lifecycle
│   ├── protocol.md              # Modbus register map + encoding tables
│   ├── installation.md          # HACS + manual + gateway prep
│   ├── smoke-test-2026-07-29.md # live-hardware smoke test log
│   └── plans/                   # implementation plans (design → tasks)
├── hacs.json                    # HACS manifest
├── pyproject.toml               # pytest + ruff config
├── LICENSE                      # MIT
├── README.md                    # this file
└── README_zh-TW.md              # 繁體中文

Dependencies

Package Version Purpose Source
pymodbus >= 3.11.2 Async Modbus TCP client https://github.com/pymodbus-dev/pymodbus
homeassistant >= 2024.10.0 Core APIs (DataUpdateCoordinator, ClimateEntity, config-flow, dispatcher) https://github.com/home-assistant/core
voluptuous (transitive via HA) Config-flow schema https://github.com/alecthomas/voluptuous

pymodbus is the only runtime dependency this integration adds. HA installs it automatically on first setup from manifest.json.requirements.

Development / test:

Package Version Purpose
pytest latest unit tests
pytest-asyncio latest async test runner (asyncio_mode = auto)
ruff latest lint, target py312, line-length 100

Testing

# From repo root
pip install pytest pytest-asyncio pymodbus voluptuous
pytest -v

Coverage:

  • tests/test_const.py — freezes the register map / mode / fan tables so a rewrite is impossible without noticing
  • tests/test_coordinator_parse.pysigned_int16, parse_gateway_meta, parse_idu_batch, _is_online heuristic
  • tests/test_coordinator_poll.py — coordinator polling loop with a mock AsyncModbusTcpClient

Integration tests against a real gateway are gated by @pytest.mark.integration:

pytest -m integration -v

Troubleshooting

Symptom Likely cause Fix
Config flow → cannot_connect Wrong IP / port, HA host can't reach gateway nc -vz <host> 502 from HA host
Config flow → invalid_device Wrong slave ID, or something else on that port Check gateway rotary switch; try slave 1
All entities unavailable after setup Gateway rebooted / LAN blip Wait 10 s — coordinator retries automatically
One IDU never appears IDU offline at setup (heuristic filtered it out) Power the IDU on — will appear at next poll
Setpoint change rejected Mode is fan_only Switch mode first, then set temperature
Fan change rejected Mode is dry Switch mode first, then set fan
Write raises IDU N offline; cannot write IDU dropped off after HA cached state Wait for reconnect; automations should check available
HA warning: via_device references non-existent gateway device Known 0.1.0 issue — tracked for pre-2025.12 fix Non-blocking; entity behaviour unaffected

Full diagnostic guide: docs/architecture.md#troubleshooting.


Roadmap

  • Register gateway "hub" device explicitly (fix via_device warning before HA 2025.12)
  • Add binary_sensor.zhijingling_vrv_online for gateway liveness (dashboard-friendly)
  • Optional climate swing mode support (if register present in future firmware)
  • i18n: English strings alongside the current 繁中 device names
  • Options flow: adjustable scan interval (currently fixed at 10 s)

Contributions and issue reports: https://github.com/WOOWTECH/Woow_ha_vrv_climate_component/issues.


License

MIT — see LICENSE.